10MW Integrated MV Skid
Jinko ESS's 10MW Integrated MV Skid integrates PCS, transformer, and RMU into a 40-ft container for plug-and-play 1500V utility storage. Featuring grid-forming, millisecond response, and high protection, it ensures maximum safety and yield in harsh environments.
Key Advantages
Highly Integrated,
Turnkey Delivery
PCS, MV transformer and ring main unit integrated in a 40-ft container for turnkey deployment.
40f
Standard Container
- 20%
Installation & Commissioning
  • Standard Container : 40f
  • Installation & Commissioning: - 20%
Active Grid-forming,
Fast Response
Active grid-forming technology with millisecond response, VSG and black start, built for weak grids.
10,000kW
Rated Power
11.000 kVA
Max Output (Short-time Overload)
  • Rated Power : 10,000kW
  • Max Output (Short-time Overload) : 11.000 kVA
Multi-layer Protection,
Ultimate Safety
Multi-level condition monitoring with electrical and mechanical interlocks plus emergency stop.
IP54
Enclosure Rating
C5
Corrosion Class
  • Enclosure Rating : IP54
  • Corrosion Class : C5
All-weather Adaptability,
Built for Extremes
Liquid-cooled PCS holds full rating at 51°C, withstanding humidity salt spray and high altitude.
51°℃
No Derating
-30℃ ~ 60℃
Operating Temperature
  • No Derating : 51°℃
  • Operating Temperature: -30℃ ~ 60℃
Specifications
DC Side Parameters
Number of DC Inputs 4 / 8
Max. DC Current per Input 4*2812 A / 8*1406 A
DC Voltage Operating Range 1000 ~ 1500V
AC Side Parameters
Rated Power 10000 kW
Max. Output Power 11000 kVA
Rated Voltage 690 Vac
Rated Grid Frequency 50/60 Hz
Power Factor -1 ~ 1 (adjustable)
Transformer Parameters
Rated Capacity 10000 kVA
Transformer Type Oil-immersed Transformer
Transformer Vector Dy11y11
Cooling Method ONAN / KNAN
LV/MV Voltage 0.69 / 10~35 kV
Top Oil / Winding Temp. Rise 55K(Top Oil) / 60K(Winding) @45℃
System Parameters
Dimensions (L×W×H) 12192 × 2438 × 2896 mm
Ambient Temperature Range -30 ~ + 60 ℃(derating >45℃)
Relative Humidity 0 ~ 100% (non-condensing)
Max. Operating Altitude 3000m (derating > 3000m)
Enclosure Protection Rati IP54
Corrosion Protection Level C4 / C5
Communication Protocol Modbus-RTU / Modbus-TCP / IEC61850 /IEC104
Compliance Standards IEC60076、EN50708、IEC62271series